Conduit Fill Calculator

Check NEC conduit fill for THHN wires in EMT conduit and find the smallest conduit size that fits.

🇺🇸 Built for United States

NEC conduit fill limits

ConductorsMax fill
153%
231%
3 or more40%
Fill % = total wire area ÷ conduit internal area

Example: six 12 AWG THHN wires (0.0133 in² each) in 3/4" EMT (0.533 in²) = 15% fill – well within the 40% limit. 3/4" EMT holds up to 16 of them.

Remember derating

With more than three current-carrying conductors in a raceway, ampacity must be reduced (80% for 4–6, 70% for 7–9).

Frequently asked questions

How many 12 AWG wires fit in 1/2" EMT?

9 THHN conductors.

Do grounding wires count toward fill?

Yes, all conductors including equipment grounds count.

Last updated 16 November 2026. Results are estimates for general information and are not financial, tax, legal or medical advice.

Related guides