Conduit Fill Calculator
Check NEC conduit fill for THHN wires in EMT conduit and find the smallest conduit size that fits.
🇺🇸 Built for United States
NEC conduit fill limits
| Conductors | Max fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| 3 or more | 40% |
Fill % = total wire area ÷ conduit internal area
Example: six 12 AWG THHN wires (0.0133 in² each) in 3/4" EMT (0.533 in²) = 15% fill – well within the 40% limit. 3/4" EMT holds up to 16 of them.
Remember derating
With more than three current-carrying conductors in a raceway, ampacity must be reduced (80% for 4–6, 70% for 7–9).
Frequently asked questions
How many 12 AWG wires fit in 1/2" EMT?
9 THHN conductors.
Do grounding wires count toward fill?
Yes, all conductors including equipment grounds count.