Voltage Drop Calculator
Calculate voltage drop in copper or aluminium cable by length, current and size (AWG or mm²), and find the minimum cable size.
Voltage drop formula
Three phase: Vd = √3 × L × I × ρ ÷ A
L is the one-way length (m), I the current (A), ρ the resistivity (copper ≈ 0.0175 Ω·mm²/m) and A the cross-section (mm²).
Example: 32 A over 30 m of 10 mm² copper at 230 V: 2 × 30 × 32 × 0.0175 ÷ 10 = 3.36 V (1.46%).
Limits
- UK (BS 7671): 3% for lighting, 5% for other circuits.
- US (NEC recommendation): 3% for a branch circuit, 5% total.
This tool also suggests the smallest cable that keeps the drop within your limit – a quick cable size calculator.
Frequently asked questions
Why does voltage drop matter?
Too much drop makes motors run hot, lights dim and wastes energy.
Does a bigger cable always help?
Yes, doubling the cross-section halves the voltage drop.
Last updated 16 November 2026. Results are estimates for general information and are not financial, tax, legal or medical advice.